{"product_id":"1-1-2-easypac-commercial-riser-groove-3-8-k2-8-testandrain-175-prv","title":"Viking EasyPac Commercial Riser 1-1\/2\" Groove 175 PRV TestanDrain","description":"\u003cdiv\u003e\n\u003ch1\u003eViking EasyPac Commercial Riser 1-1\/2\" Groove with 175 PRV and TestanDrain\u003c\/h1\u003e\n\u003cp\u003eThe Viking EasyPac Commercial Riser is a pre-assembled, factory-tested 1-1\/2\" riser manifold designed for commercial wet-pipe fire sprinkler systems, particularly suitable for high-rise buildings and floor control zones. This all-in-one unit simplifies installation and ongoing maintenance by integrating crucial fire protection components into a single assembly.\u003c\/p\u003e \u003cul\u003e\n\u003cli\u003e\n\u003cb\u003eSize and Connections\u003c\/b\u003e: This model features a 1-1\/2\" pipe size with grooved inlet and outlet connections, engineered for quick, secure, and rigid installation within compatible piping systems. It is constructed from Schedule 10 steel pipe.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003eIntegrated TESTanDRAIN Valve\u003c\/b\u003e: Includes an AGF TESTanDRAIN valve that combines the functions of an inspector's test connection and a system drain. This valve typically features a test orifice and sight glass for visual confirmation of water flow.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003ePressure Relief Valve (PRV)\u003c\/b\u003e: Equipped with a factory-set 175 PRV, which is required by NFPA 13 for all wet-pipe systems, protecting the system from damaging overpressure. The PRV is designed to open in a pressure range between 90% and 105% of its 175 rating and close above 80% of that rating.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003eAdditional Components\u003c\/b\u003e: The assembly includes pressure gauges, a Potter water flow switch for reliable alarm activation, and a 3-way gauge control valve, all within a durable fabricated steel body.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003ePressure Rating\u003c\/b\u003e: This riser assembly has a maximum water working pressure rating of 250 PSI (17.2 bar).\u003c\/li\u003e\n\u003c\/ul\u003e \u003cp\u003eThis Viking EasyPac Riser streamlines fire protection system management and offers a professional, uniform appearance. Its integrated design eliminates the need to purchase and assemble individual parts on-site, saving significant time and labor during installation. The built-in test port allows for hydrostatic testing without draining the entire system, and the configuration also removes the need to drain the system before installing the relief valve. It ensures high performance and full compliance with NFPA 13 and NFPA 25 requirements.\u003c\/p\u003e\n\u003c\/div\u003e","brand":"Viking","offers":[{"title":"Default Title","offer_id":50062373552376,"sku":"14878A175","price":1074.27,"currency_code":"USD","in_stock":true}],"url":"https:\/\/fireprotectionparts.net\/es\/products\/1-1-2-easypac-commercial-riser-groove-3-8-k2-8-testandrain-175-prv","provider":"Fire Protection Parts","version":"1.0","type":"link"}